Group connected loads by voltage rail

Record each device’s supply voltage and input consumption for the relevant operating state. Multiply the per-device figure by the quantity. If the input is specified in watts, use I = P/U on the DC rail. Keep 12 V and 24 V loads on separate rails. A rail fed through a DC/DC converter adds an upstream load that depends on converter efficiency and its own consumption.

Work through a simultaneous operating scenario

A teaching example uses a 24 V PLC rated at 250 mA, a 6 W HMI, four 25 mA sensors and two 150 mA valves. With everything enabled, the HMI draws 0.25 A and the scenario totals 0.90 A or 21.6 W. A chosen 25% margin gives a steady-state demand of 27 W, or 1.125 A at 24 V.

If the valves operate alternately, put them into separate groups and evaluate both states. Where peak device current is known, enter it for that group and check which peaks may coincide. Peak demand remains unknown when the device data is unavailable.

Check the supply at the actual conditions

Verify overload duration, voltage at the load terminals and derating at the intended ambient temperature and mounting conditions. The 25% margin belongs to the example. Select and protect the power supply circuits using the relevant equipment information.

Open the 24 V load calculator · Phoenix Contact supply data with derating curves