Start with one conductor’s resistance
Enter the one-way route length. Given ρ₂₀ in Ω·mm²/m, one conductor’s resistance is R = ρ₂₀[1 + α(T − 20)]L/S. Use the conductor temperature for T. Ambient temperature may differ. For real installations, prefer the cable manufacturer’s resistance and reactance data per unit length.
A worked estimate of voltage and losses
For 50 m of 4 mm² copper at 20 °C and ρ₂₀ = 0.01724 Ω·mm²/m, one conductor has R = 0.2155 Ω. In a single-phase 230 V circuit at 16 A and unity power factor, the outgoing and return conductors produce approximately 6.90 V drop, or 3.00%. The resistive loss is about 110 W. Entering loop length instead of one-way length would double the result in this model.
For a balanced three-phase load, approximate the line-to-line drop as √3IR cos φ. Resistive losses in the three phase conductors are 3I²R. R still refers to one conductor.
When the full calculation is needed
This approximation omits reactance and assumes uniform conductor temperature. For long runs, large drops, unusual power factor or starting conditions, use the actual cable and load characteristics. Check ampacity, heating, installation conditions, protection and disconnection independently under applicable requirements.
Open the voltage drop calculator · Schneider Electric Electrical Installation Guide