← All tools

Cable Voltage Drop

Estimate voltage drop and power loss from current, one-way length, conductor area, material and temperature.

Inputs

Worked example · 50 m copper line, 4 mm², 16 A, 20 °C

How the calculation works

R = ρ₂₀ × [1 + α × (T − 20)] × L / S. R is one conductor’s resistance, ρ₂₀ in Ω·mm²/m, α in 1/°C, L the one-way length in m and S the area in mm². Single-phase ΔU ≈ 2IRcos φ and losses 2I²R use both outgoing and return conductors. Balanced three-phase ΔU ≈ √3IRcos φ and losses 3I²R.