Convert current to a measurement

For a linear transmitter, 4 mA is the lower signal endpoint and 20 mA the upper endpoint. With I in mA, the fraction of span is (I − 4)/16. Multiply this fraction by the difference between the engineering endpoints and add the value at 4 mA.

A 0–10 bar teaching example reads 5 bar at 12 mA, or 50% of the span. On a reversed scale with 10 bar at 4 mA and 0 bar at 20 mA, 8 mA represents 7.5 bar. For the inverse, start with the fraction of the engineering span.

Treat range and diagnostics separately

A current below 4 mA or above 20 mA can be extrapolated mathematically. Its validity as a measurement depends on the transmitter and receiver. Use their manuals to configure under-range, over-range and fault detection. Evaluate the measurement quality flag separately if your input module supplies one.

Check the loop voltage budget

The same current flows through series elements. A two-wire transmitter needs enough supply voltage for its minimum terminal voltage and the drops across the input shunt, cable and barriers. For example, a 250 Ω shunt drops 5 V at 20 mA. Compare the full budget with device data at the highest expected current.