Separate electrical input and mechanical output
With balanced sinusoidal steady-state conditions, S = √3 × Uₗ × Iₗ, where Uₗ is line-to-line RMS voltage and Iₗ is line RMS current. Active power is P₁ = S cos φ. The shaft output is P₂ = ηP₁, with efficiency η expressed as a fraction. Measure apparent power in VA, active power in W and reactive power in var.
Work a 400 V example
A motor delivering 5.5 kW at 90% efficiency and 0.82 power factor receives about 6.11 kW of active input. At 400 V line-to-line, the estimated current is 10.76 A. Efficiency and power factor are supplied teaching inputs. For real calculations, obtain them from the data sheet or measurements at the relevant operating point.
Relate speed and torque to the operating point
At 50 Hz a four-pole motor has a synchronous speed of 1,500 rpm. A slip of 4% gives an estimated rotor speed of 1,440 rpm. At that speed, 5.5 kW at the shaft corresponds to about 36.47 N·m. Starting current, unbalance and drive harmonics are outside this model. Drive input current and motor current at its output belong to different circuits.
Power and current · Frequency and speed · Shaft torque · Schneider Electric power equations · ABB drive dimensioning guide