Single- and Three-Phase Power
Calculate active, apparent and reactive power, current or cos φ. For motors, enter shaft power and efficiency to find input current.
Result
How the calculation works
S = k × U × I, P₁ = S × cos φ, |Q| = S × √(1 − cos² φ). k is 1 or √3. U is in V, I in A, P₁ and P₂ in W, S in VA and Q in var. For a motor, P₁ = P₂ / η, where η is a fraction.